Technical facts: IVT Greenline HE

ModelC6 / E6C7 / E7C9 / E9C11/E11E14E17

Operating liquid / water

Heat output (B0 / W35) 1)5.5 kW7.2 kW8.8 kW10.3 kW14.8 kW16.4 kW

COP (B0 / W35) 1)4.24.54.44.0

Brine

Nominal flow0.30 l / s0.38 l / s0.46 l / s0.57 l / s0.78 l / s0.90 l / s

Max. pressure4 bar

Operating temperature-5 - +20 ° C

Connection (Cu)28 mm35 mm

Compressor

TypeScroll

Weight refrigerant R407c1.6 kg1.8 kg2.4 kg2.3 kg

Heater

Nominal flow0.18 l / s0.23 l / s0.29 l / s0.34 l / s0.47 l / s0.54 l / s

Min. / Max. supply temperature20/65 ° C

Max. permissible operating pressure1.5 bar

Connection (Cu)22 mm28 mm

Hot water

Volume water heater C-model185/40 L-

Preparer C modelCu / RfRf

Connection (Cu / Rf)22 mm28 mm

Values ​​for electrical connection

Wiring400V 3N ~ 50Hz

Additional heat switchable 3)1-3 / 6/9 KW

Electric cassette <3 kW1620

Cassette 6 kW162025

Immersion heater 9 kW202535

Degree of protectionX1

Generally

Sound output C model 2)44 dBA47 dBA49 dBA48 dBA-

Sound effect E-model 2)47 dBA50 dBA51 dBA48 dBA51 dBA47 dBA

ControllerRego 1000

Dimensions (widthxdepthxheight) C-model600 × 645 × 1800 mm

Dimensions (widthxdepthxheight) E-model600 × 645 × 1520 mm

Weight (without packaging) C-model230/200 kg231/201 kg240/210 kg218 kg-

Weight (without packaging) E-model146 kg152 kg155 kg170 kg190 kg195 kg

1) ACCORDING TO EN 14511 
2) ACCORDING TO EN ISO 3743-1 
3) OPTION 1,2 OR 3 KW FOR BBR NYBYGGNATIONSREGLER 

Ground Source Heat Pump Technical

Energy Superstore Nationwide

We have over 30 year’s experience in Renewable Energy Products

Wood Pellets Heat Pumps, Solar Panels, HRV and Underfloor Heating

© Energy Superstore Ltd., Cappincur, Tullamore, Co. Offaly. CRO No 192236

 

Email: info@energysuperstore.ie  Phone: 057 93 24062

Lo Call: 1800 311338