Technical facts: IVT Greenline HE

ModelC6 / E6C7 / E7C9 / E9C11/E11E14E17

Operating liquid / water

Heat output (B0 / W35) 1)5.5 kW7.2 kW8.8 kW10.3 kW14.8 kW16.4 kW

COP (B0 / W35) 1)4.24.54.44.0

Brine

Nominal flow0.30 l / s0.38 l / s0.46 l / s0.57 l / s0.78 l / s0.90 l / s

Max. pressure4 bar

Operating temperature-5 - +20 ° C

Connection (Cu)28 mm35 mm

Compressor

TypeScroll

Weight refrigerant R407c1.6 kg1.8 kg2.4 kg2.3 kg

Heater

Nominal flow0.18 l / s0.23 l / s0.29 l / s0.34 l / s0.47 l / s0.54 l / s

Min. / Max. supply temperature20/65 ° C

Max. permissible operating pressure1.5 bar

Connection (Cu)22 mm28 mm

Hot water

Volume water heater C-model185/40 L-

Preparer C modelCu / RfRf

Connection (Cu / Rf)22 mm28 mm

Values ​​for electrical connection

Wiring400V 3N ~ 50Hz

Additional heat switchable 3)1-3 / 6/9 KW

Electric cassette <3 kW1620

Cassette 6 kW162025

Immersion heater 9 kW202535

Degree of protectionX1

Generally

Sound output C model 2)44 dBA47 dBA49 dBA48 dBA-

Sound effect E-model 2)47 dBA50 dBA51 dBA48 dBA51 dBA47 dBA

ControllerRego 1000

Dimensions (widthxdepthxheight) C-model600 × 645 × 1800 mm

Dimensions (widthxdepthxheight) E-model600 × 645 × 1520 mm

Weight (without packaging) C-model230/200 kg231/201 kg240/210 kg218 kg-

Weight (without packaging) E-model146 kg152 kg155 kg170 kg190 kg195 kg

1) ACCORDING TO EN 14511 
2) ACCORDING TO EN ISO 3743-1 
3) OPTION 1,2 OR 3 KW FOR BBR NYBYGGNATIONSREGLER 

Ground Source Heat Pump Technical